Open phase fault
The open phase fault stops the motor when one of the three motor phases appears to be disconnected or loose. The controller compares the currents in the three phases while running.
Prerequisites
Prerequisites
- Motor setup is complete and the motor runs correctly.
How it works
When open phase fault detection is enabled, the controller compares the RMS currents of the three phases. If the difference between any two phases is greater than Open Phase Fault Detection Threshold for more than 1 second, the controller sets Open Phase Fault (Faults2 bit 14) and disables the motor phase bridge.
The fault clears with a fault clear command or a key cycle.
Configure the open phase fault
- Enable
Level 1 Featuresbit 2 Open phase fault detection. - Set
Open Phase Fault Detection Thresholdto the phase current difference, in amperes, that should trigger the fault. - Save the parameters to flash.
To disable the open phase fault, disable Level 1 Features bit 2 Open phase fault detection.
Verify
- Run the motor through its normal load range.
- Check that
Faults2bit 14 does not set in normal operation. If it does, check the phase connections before you raise the threshold.
Troubleshooting
The fault triggers in normal operation
Check and fix the motor phase connections at the controller and the motor. One phase is likely disconnected or loose. If all connections are good, the threshold may be too low for your motor.
Parameters
| Parameter | Address | Units | Description |
|---|---|---|---|
Level 1 Features |
1880 | Bit field. Bit 2: Open phase fault detection. | |
Open Phase Fault Detection Threshold |
1966 | A | Phase RMS current difference that triggers the open phase fault. |