CANopen calculator
Use these calculators to find the CANopen message IDs of a controller, to convert a Modbus address to a CANopen index and sub-index, and to make or decode SDO messages. The parameter names, units and scales are from the Modbus parameter dictionary.
Prerequisites
- You know the node ID of the controller (
CAN ID). The default is 42 (0x2A). - You know the CANopen basics on CANopen protocol reference.
The calculators on this page all use this node ID.
Message IDs
| Message | COB-ID |
|---|---|
| NMT command | 0x000 |
| Emergency (EMCY) | - |
| TPDO1, TPDO2, TPDO3, TPDO4 | - |
| RPDO1, RPDO2, RPDO3, RPDO4 | - |
| SDO response (from the controller) | - |
| SDO request (to the controller) | - |
| Heartbeat | - |
The PDO COB-IDs are correct only when the controller sets them from the node ID (Communications Configuration Vector bits 5 and 6). Refer to Process Data Objects.
Address conversion
Enter a Modbus address, or an index and sub-index. The other fields change.
SDO messages
Make a request
The request uses the Modbus address in "Address conversion". The scale comes from the parameter dictionary. You can change it. For a bit field or a hex value, enter the raw value, for example 0x0020.
| Message | COB-ID | Length | Data bytes 0 to 7 |
|---|---|---|---|
| Read request | 8 | ||
| Write request | 8 |
Decode a response
Copy the eight data bytes from your CAN tool. Separate them with spaces.
How it works
The controller maps each Modbus address to a CANopen index and sub-index:
| Value | Formula |
|---|---|
| Index | 0x2000 + FLOOR(Modbus address / 64) |
| Sub-index | REMAINDER(Modbus address / 64) + 1 |
Modbus address to CANopen index and sub-index
CANopen data is little-endian. The least significant byte is first.
A parameter value is a signed 16-bit integer (−32768 to 32767), unless the parameter dictionary says otherwise: raw value = value × scale. For example, battery voltage (address 265) has a scale of 32. A raw value of 0x0600 (1536) is 1536 / 32 = 48 V.
The calculator writes with command 0x2B (two data bytes). For the message format, the response codes and the error codes, refer to Service Data Objects.
Parameters
| Parameter | Address | Units | Description |
|---|---|---|---|
CAN ID |
57 | Node ID, 1 to 127. The default is 42 (0x2A). | |
Communications Configuration Vector |
58 | Bit field. Bits 5 and 6 set the TPDO and RPDO COB-IDs from the node ID. |
Parameters used on this page