EN 15194 safety protocol
An EN controller has a firmware safety protocol for electrically power-assisted cycles (EPAC). The protocol stops the controller if the power bridge operates without pedalling. It helps you to get EN 15194 approval for your bicycle. This page tells you how the protocol operates and how to configure your controller to operate with it.
Prerequisites
Prerequisites
- The controller is an EN controller:
TE Configurationis 1 (Pedal bikes (ISO13849)). Only the ASI end-of-line tester can set this value. If you need an EN controller, contact ASI when you order. - The motor is a one-way (clutched) motor.
- The pedal sensor is set up.
When to use this
Use this page if your controller is an EN controller and your vehicle is an EPAC that must meet EN 15194.
The protocol meets or exceeds performance level PLr c of ISO 13849-1:2015 for these EN 15194 safety functions:
| Safety function ID | Safety function |
|---|---|
| SF-A | Prevention of an unintentional self-start of the EPAC |
| SF-B | Prevention of motor assistance without pedalling and without the start-up assistance mode (walk mode) |
Safety functions of the EN protocol
Note
The controller meets ISO 13849 for firmware safety only. The complete bicycle must meet and pass the EN 15194 requirements. Safety is the sole responsibility of the system integrator.
How it works
The controller monitors these items:
- The PWM of the power bridge.
- The pedal sensor input.
- Commands from a peripheral device, for example a display, that start walk mode.
If the PWM is outside its idle range, the controller sees this as power bridge activity. It then expects pedal input or walk mode. If there is no valid pedal input and walk mode is not active, the controller goes to a safe state. This occurs in 2 seconds or less.
In the safe state, the motor does not operate and the controller does not respond. To return to usual operation, disconnect and connect the power again.
Configure the controller for the EN protocol
Some features supply motor current without pedal input. On an EN controller, they cause the safe state. Configure the controller as follows:
- Make sure that the motor is a one-way (clutched) motor. A direct-drive motor, or a motor with a clutch that does not release, makes back-EMF when the bicycle coasts. The back-EMF moves the PWM outside its idle range, and the controller sees this as power bridge activity without pedal input.
-
Set
Control command sourceto 2 (Pedal sensor). Refer to Pedal sensors.Note
You can also use 4 (Throttle OR pedal sensor), but we do not recommend it. If the rider uses the throttle without pedalling, the controller goes to the safe state.
-
Set
Pedalec minimum timeoutandPedalec maximum timeoutso that the motor assistance stops in less than 2 seconds after the rider stops pedalling. A longer time causes the safe state. Refer to Pedal sensors. - Set
Minimum motoring torqueto 0. Refer to Minimum motoring torque. - If you use walk mode, use a network command with a heartbeat. Refer to Walk mode.
- Set the vehicle speed limits to 27.5 km/h or less.
- Enable the write lock, so that users cannot change the parameters. Refer to Parameter read/write lock.
- Save the parameters to flash.
Verify
- Make sure that
TE Configurationis 1. - Ride the bicycle and pedal. Make sure that the motor supplies assistance.
- Stop pedalling. Make sure that the assistance stops and that the controller does not go to the safe state.
- Let the bicycle coast. Make sure that the controller does not go to the safe state.
- If you use walk mode, start it. Make sure that the motor operates and that the controller does not go to the safe state.
Troubleshooting
The motor stops and the controller does not respond until a power cycle
The controller is in the safe state. It found power bridge activity without pedal input. Possible causes:
- The motor is a direct-drive motor, or its clutch does not release.
- The rider used the throttle without pedalling (
Control command source4). Pedalec minimum timeoutorPedalec maximum timeoutis too long.Minimum motoring torqueis more than 0.- Walk mode is started without a network command and heartbeat.
Correct the cause. Then disconnect and connect the power again.
Parameters
| Parameter | Address | Units | Description |
|---|---|---|---|
TE Configuration |
2047 | 1 (Pedal bikes (ISO13849)) on an EN controller. Set by ASI only. | |
Control command source |
208 | Command input. Use 2 (Pedal sensor). | |
Pedalec minimum timeout |
232 | ms | Minimum time before assistance stops when the pedals do not move. Assistance must stop in less than 2 seconds. |
Pedalec maximum timeout |
233 | ms | Maximum time before assistance stops when the pedals do not move. Assistance must stop in less than 2 seconds. |
Minimum motoring torque |
173 | pu A | Set to 0 on an EN controller. |