CANopen setup

Use this page to set up CAN communication on the controller. Use it when your system controls or monitors the controller over a CAN bus. For example, a vehicle control unit, a display or a battery management system (BMS) can use the CAN bus.

This page gives:

  • The minimum settings to put the controller on a CAN bus.
  • The bus termination.
  • How to read and write parameters with Service Data Objects (SDOs).
  • How to set up Process Data Objects (PDOs).
  • An example setup for remote speed control.
  • How to use more than one controller on a bus.

For the message formats and all the CAN settings, refer to the CANopen protocol reference.

Quick start

This section gives the minimum settings to put the controller on a CAN bus. It also gives an example setup for remote speed control. For full details of each message type, refer to the CANopen protocol reference.

ASI CANopen data is little-endian: the controller sends the least significant byte first.

Enable CAN

  1. Set CAN baud rate (address 56) to the bus speed: 1000, 500, 250 or 125 kbps. The default is 250 kbps.
  2. Set CAN ID (address 57) to a node ID from 1 to 127 that is unique on the bus. The default is 42 (0x2A).
  3. Check that Communications Configuration Vector (address 58) bit 7 CAN Enable is enabled. CAN does not work without this bit. This bit is enabled in the default parameters.
  4. Check Communications Configuration Vector bit 4 auto operational. When this bit is enabled, the controller moves to the Operational state without network management (NMT) messages. If CAN heartbeat period (address 1866) is set, it moves one state per heartbeat. Otherwise, it moves immediately. This bit is enabled in the default parameters.

    CAN heartbeat period (address 1866) sets how often the controller sends its own heartbeat message, in ms. 0 turns it off. The default value is 0.

  5. Optional: enable Communications Configuration Vector bit 0 Extended 29bit ID to use 29-bit extended CAN IDs.

  6. Save to flash, then power cycle the controller.

Terminate the bus

A CAN bus must have exactly two 120 Ω termination resistors, one at each end of the bus. With the bus power off, measure the resistance between CAN-H and CAN-L. The correct value is approximately 60 Ω.

We recommend that you put the termination resistors in the harness. You cannot measure the configurable termination inside the controller. This makes troubleshooting more difficult.

The controller has an internal termination resistor. In the default parameters it is disconnected (Communications Configuration Vector bit 12 Disable CAN termination resistor is enabled). If you use it instead of a harness resistor, disable bit 12 to connect the resistor. Use it only when the controller is at one end of the bus.

Read and write parameters with SDOs

You can read or write every parameter in the Modbus parameter dictionary over CAN with Service Data Objects (SDOs). Convert the Modbus address to a CANopen index and sub-index:

Value Formula
Index FLOOR(Modbus address / 64) + 8192
Sub-index REMAINDER(Modbus address / 64) + 1

Modbus address to CANopen index and sub-index

Parameter Modbus address Index Sub-index
Communications Configuration Vector 58 8192 (0x2000) 59 (0x3B)
Remote state command 493 8199 (0x2007) 46 (0x2E)
TPDO1 size (words) 1824 8220 (0x201C) 33 (0x21)

Conversion examples

CAN message IDs

The controller uses the standard CANopen message IDs (COB-IDs), based on its node ID.

Message COB-ID Example for node ID 42
NMT command 0x000 0x000
Emergency (EMCY) 0x080 + node ID 0x0AA
TPDO1 to TPDO4 0x180, 0x280, 0x380, 0x480 + node ID 0x1AA, 0x2AA, 0x3AA, 0x4AA
RPDO1 to RPDO4 0x200, 0x300, 0x400, 0x500 + node ID 0x22A, 0x32A, 0x42A, 0x52A
SDO response 0x580 + node ID 0x5AA
SDO request 0x600 + node ID 0x62A
Heartbeat 0x700 + node ID 0x72A

Standard COB-IDs

Set up PDOs

Process Data Objects (PDOs) send or receive up to four parameters in one message. The controller sends transmit PDOs (TPDOs) and receives receive PDOs (RPDOs).

In the default parameters, only TPDO1 is set up. It sends controller status, battery voltage, motor rpm and motor current every 100 ms on COB-ID 0x1AA (0x180 + node ID 42). For the data layout, refer to the TPDO1 tab in Example: remote speed control. All other PDOs are off. To set up more PDOs:

  1. Enable Communications Configuration Vector bit 5 Autoset CANopen COBID for TPDOs and bit 6 Autoset CANopen COBID for RPDOs. The controller then sets the COB-IDs of PDOs 1 to 4 from its node ID, as shown in CAN message IDs. These bits are off in the default parameters, so if you change CAN ID without them, TPDO1 still sends on 0x1AA.

    If you do not use these bits, set each PDO COB-ID yourself. The COBID (low word) parameter is the COB-ID. The COBID (high word) parameter holds control bits. Set it to 0x0000 unless you use one of these features:

    Bit TPDO RPDO
    15 PDO disable PDO disable
    14 RTR enable: transmit when an RTR frame is received Reserved
    13 Extended ID Extended ID

    PDO COBID (high word) control bits

  2. For each parameter in the PDO, set a map index and a map sub-index and size:

    • Map index: the CANopen index of the parameter.
    • Map sub index and size: the sub-index in the high byte and the size in bits in the low byte. For a 16-bit parameter, the low byte is 0x10.

    For example, to map Remote state command (address 493), set the map index to 0x2007 and the map sub index and size to 0x2E10.

  3. Set the PDO size (words) to the number of mapped parameters.

  4. Set the transmission type:
    • TPDO: set the transmission type to 0 and the event time to the send period in ms. To send on SYNC instead, set the transmission type to N to send on every Nth SYNC.
    • RPDO: set the transmission type to a non-zero value to enable the RPDO. 0 disables it.
  5. Save to flash, then power cycle the controller.

Command timeouts

For remote control, you must send Remote state command with a rolling watchdog counter in its high byte, within the command timeout thresholds. For the message format and the recommended thresholds, refer to Command timeouts.

Example: remote speed control

This example sets up the controller to receive speed and current-limit commands from a vehicle control unit. The controller also sends status, temperatures and faults back. It uses the PDO COB-IDs that are set automatically from the node ID.

Prerequisites

  • CAN is enabled and the bus is terminated, as described above.
  • Communications Configuration Vector bits 5 and 6 are enabled.
  • Control command source (address 208) is set to 0 / Remote.
  • Speed regulator mode (address 11) is set to 0 / Speed.
  • The command timeouts are set. Refer to Command timeouts.

For how the controller uses each remote command, refer to Remote motor control.

In the tables below, a scale of 40.96 means that a raw value of 4096 is 100%. A scale of 32 means that a raw value of 32 is 1 unit.

Sent by your control unit to 0x200 + node ID, on every heartbeat.

Bytes Parameter Address Scale Unit
0 Remote state command (low byte) 493 1 0 = Off, 1 = Idle, 2 = Run
1 Watchdog counter (high byte of Remote state command) 493 1 Rolling counter, 0 to 255
2, 3 Remote maximum motoring current 491 40.96 % of Rated motor current
4, 5 Remote maximum braking current 492 40.96 % of Rated motor current
6, 7 Remote speed command 490 40.96 % of Rated motor speed, signed. Negative values command reverse

RPDO1 data

Parameter Address Value
RPDO1 map1 index 1793 0x2007
RPDO1 map1 sub index and size 1792 0x2E10
RPDO1 map2 index 1795 0x2007
RPDO1 map2 sub index and size 1794 0x2C10
RPDO1 map3 index 1797 0x2007
RPDO1 map3 sub index and size 1796 0x2D10
RPDO1 map4 index 1799 0x2007
RPDO1 map4 sub index and size 1798 0x2B10
RPDO1 size (words) 1800 4
RPDO1 transmission type 1801 1

RPDO1 settings

Example

For node ID 42, the frame 0x22A 01 0A 00 08 66 0E 33 0F decodes as:

  • 01: Idle.
  • 0A: watchdog counter 10.
  • 00 08 (0x0800 = 2048): 2048 / 40.96 = 50% maximum motoring current.
  • 66 0E (0x0E66 = 3686): 90% maximum braking current.
  • 33 0F (0x0F33 = 3891): 95% of rated motor speed, forward.

Sent by your control unit to 0x300 + node ID.

Bytes Parameter Address Scale Unit
0, 1 remote maximum battery current limit 360 8 A. If non-zero, used when lower than the battery current limit
2, 3 remote maximum regen battery current limit 361 8 A. If non-zero, used when lower than the regeneration battery current limit

RPDO2 data

Parameter Address Value
RPDO2 map1 index 1805 0x2005
RPDO2 map1 sub index and size 1804 0x2910
RPDO2 map2 index 1807 0x2005
RPDO2 map2 sub index and size 1806 0x2A10
RPDO2 size (words) 1812 2
RPDO2 transmission type 1813 1

RPDO2 settings

Sent by the controller from 0x180 + node ID, every 100 ms. This is the same as the default TPDO1.

Bytes Parameter Address Scale Unit
0, 1 controller status 257 1 0 = Pre-Operational, 1 = Idle, 2 = Post Operational, 3 = Run, 4 = Fault
2, 3 battery voltage 265 32 V
4, 5 motor rpm 263 1 RPM
6, 7 motor current 262 32 A

TPDO1 data

Parameter Address Value
TPDO1 map1 index 1817 0x2004
TPDO1 map1 sub index and size 1816 0x0210
TPDO1 map2 index 1819 0x2004
TPDO1 map2 sub index and size 1818 0x0A10
TPDO1 map3 index 1821 0x2004
TPDO1 map3 sub index and size 1820 0x0810
TPDO1 map4 index 1823 0x2004
TPDO1 map4 sub index and size 1822 0x0710
TPDO1 size (words) 1824 4
TPDO1 transmission type 1825 0
TPDO1 event time 1826 100

TPDO1 settings

Example

For node ID 42, the frame 0x1AA 04 00 03 06 00 00 02 00 decodes as:

  • 04 00: Fault.
  • 03 06 (0x0603 = 1539): 1539 / 32 = 48.09 V.
  • 00 00: 0 RPM.
  • 02 00 (0x0002 = 2): 2 / 32 = 0.0625 A.

Sent by the controller from 0x280 + node ID, every 100 ms.

Bytes Parameter Address Scale Unit
0, 1 controller temperature 259 1 °C, signed
2, 3 motor temperature 261 1 °C, signed
4, 5 battery current 266 32 A, signed. Positive is current from the battery into the controller
6, 7 motor input power 334 1 W, signed. Positive is power into the motor

TPDO2 data

Parameter Address Value
TPDO2 map1 index 1829 0x2004
TPDO2 map1 sub index and size 1828 0x0410
TPDO2 map2 index 1831 0x2004
TPDO2 map2 sub index and size 1830 0x0610
TPDO2 map3 index 1833 0x2004
TPDO2 map3 sub index and size 1832 0x0B10
TPDO2 map4 index 1835 0x2005
TPDO2 map4 sub index and size 1834 0x0F10
TPDO2 size (words) 1836 4
TPDO2 transmission type 1837 0
TPDO2 event time 1838 100

TPDO2 settings

Sent by the controller from 0x380 + node ID, every 500 ms. Each value is a bit vector. For the bit definitions, refer to Faults and warnings.

Bytes Parameter Address
0, 1 faults 258
2, 3 faults2 299
4, 5 warnings 277

TPDO3 data

Parameter Address Value
TPDO3 map1 index 1841 0x2004
TPDO3 map1 sub index and size 1840 0x0310
TPDO3 map2 index 1843 0x2004
TPDO3 map2 sub index and size 1842 0x2C10
TPDO3 map3 index 1845 0x2004
TPDO3 map3 sub index and size 1844 0x1610
TPDO3 size (words) 1848 3
TPDO3 transmission type 1849 0
TPDO3 event time 1850 500

TPDO3 settings

Several controllers on one bus

Each controller on the bus must have a unique node ID. To use the same parameter file on two controllers, enable Communications Configuration Vector bit 13 Enable automatic CAN ID adjustment. At start-up, the controller adds to its CAN ID:

  • 1 if the Cruise input is high.
  • 2 if the PFS input is high.
  • 3 if both inputs are high.

To check the node ID in use, read can auto ID (address 1676).

J1939

The BAC6 controllers use CANopen. J1939 is available on our BAC8 product family. For more information, contact your ASI sales representative.

Protocol reference

For the message formats (SDO, NMT, SYNC, heartbeat, EMCY), all CAN settings and more PDO examples, refer to the CANopen protocol reference.

Fault and warning settings

  • CAN bus fault and CAN Bus warning (Faults2 bit 5 and Warnings bit 4): to disable both, disable Communications Configuration Vector bit 1 CAN faults (address 58).
  • Remote CAN fault (Faults2 bit 12): you cannot disable it while Communications Configuration Vector bit 7 CAN enable is enabled.
  • Missed CAN Message (Warnings2 bit 7): you cannot disable it.