Command Timeouts

Overview

Command timeouts are used to protect from frozen frames from remote devices. This is accomplished by sending a changing value to the high-byte of Remote state command, typically a rolling high-byte is used. E.g. Incrementing the high-byte on each heartbeat (0x0100, 0x0200, 0x0300 ... 0xFF00), instead of alternating two values. The time between changing values of this high-byte are compared instantaneously against Command timeout threshold or the average of the last 100 samples against Average Command timeout threshold.

Application notes

Generally, you do not want to set the average to your actual heartbeat time-period or you risk nuisance trips. You might have a heartbeat of 200ms, set your average to 250ms and your instantaneous to 1000ms. So, that any 100 samples do not average greater than 250ms and any instantaneous heartbeat is not longer than 1000ms. Adjust these based on your safety requirements accordingly.

Configuration

  1. Set Command timeout threshold to a non-zero value for instantaneous timeout faults (1 sample).
  2. Set Average Command timeout threshold to a non-zero value, for averaged timeout faults (100 samples).

FAQ

Can Command Timeout Threshold (1 sample) and Average command timeout threshold (100 samples) be made to respect remote Modbus or CANopen writes or is there some other parameter we should use?

You must send a rolling counter on the high byte of Remote state command on a heartbeat within the timeout thresholds.

Byte Function Notes
Low byte Remote State Command 0 = Off, 1 = Idle, 2 = Active
High byte Watchdog Counter Rolling Counter from 0 to 255

Can CAN sync loss fault motor?

If CAN sync loss timeout is not respected (RPDO), and Command timeout threshold (1 sample) and Average Command timeout threshold (100 samples) are set (typically 1000 ms and 250 ms respectively). It will trigger the Faults bit 8 Network communication timeout fault which causes the motor to be disabled until the controller is power cycled, and the LED should flash a 2, 1 sequence while faulted.

How do you use Remote network voltage for throttle when running in local mode (e.g. Control command source = throttle or pedal and throttle) when Command timeout threshold (1 sample) and Average Command timeout threshold (100 samples) are set?

You must send a heartbeat, rolling counter, on the Remote state command above 255. e.g., A rolling counter on the high byte (0x0100, 0x0200, 0x0300 ... 0xFF00)

Communication loss braking?

If the communication loss fault triggers, it will initiate braking to 0 only if in remote speed mode, Control command source = 0 (serial stream) and Speed regulator mode = 0 (speed). The braking current is limited by Remote comm loss braking current as a function of rated motor current for braking. Braking will occur for 10 seconds.

It does not trigger in other modes, i.e., Control command source is not set to 0 (serial stream)