Faults

Faults Table

Fault Cause Behaviour
Low Field Strength Magnetic field either too weak or not present Sensor will report 0º and 0%, appropriate fault codes 0x08 are set
Redundancy Fault Disagreement between redundant sensors Sensor will report 0º and 0%, appropriate fault codes are set
Sensor Link Fault Internal sensor communication lost Sensor will report 0º and 0%, appropriate fault codes 0x08 are set
Sensor Internal Fault Numerous Sensor will report 0º and 0%, appropriate fault codes are set
Travel Bounds Fault Angle is outside the specified relative deadbands Sensor will report measured and calibrated angles as usual but will report 0% relative travel, appropriate fault codes are set

Clearing Faults

Faults are cleared by a power cycle or by sending a fault clear command (see Software Interface section for more information).